## Project : ISTTOK slow Control
|
||
##
|
||
## File :
|
||
## Description : Records for ISTTOK Control I/O channels connected to 2 Velleman board
|
||
##
|
||
##
|
||
## Author : Bernardo Carvalho (IPFN-IST)
|
||
##
|
||
## Copyright (c) : IPFN-IST 2015-2020
|
||
## Created 3-Mar-2019
|
||
##
|
||
##
|
||
##########################################
|
||
|
||
################
|
||
###############
|
||
# REGISTER 56 #
|
||
###############
|
||
###############
|
||
|
||
#####################################
|
||
### 24V commands - Optocoupler Out###
|
||
#####################################
|
||
record(bo, "$(P)$(R)TMPump1-ControllerOn" ) {
|
||
field(DESC,"Signal to TMP 1, goes HIGH and LW")
|
||
field(ZNAM, "Off" )
|
||
field(ONAM, "Pulse" )
|
||
field(HIGH, "2.5")
|
||
# Disabled until further notice
|
||
# field(FLNK, "$(P)$(R)TMPump1-ControllerOnInv" )
|
||
field(VAL,"0")
|
||
}
|
||
record(calcout, "$(P)$(R)TMPump1-ControllerOnInv") {
|
||
field(INPA, "$(P)$(R)TMPump1-ControllerOn NPP MS")
|
||
field(OUT, "$(P)$(R)PCF8574:56:REGISTER.B0 PP MS")
|
||
field(OOPT, "On Change")
|
||
field(CALC, "A?0:1")
|
||
}
|
||
|
||
record(bo, "$(P)$(R)TMPump1-ControllerOff" ) {
|
||
# field(DESC," Sinal p/ TMP 1, desliga a alimentação do controlador, LOW->HIGH-> LOW")
|
||
# record(bo, "$(P)$(R)TMPControllerOff" ) {
|
||
field(ZNAM, "Off" )
|
||
field(ONAM, "Pulse" )
|
||
field(HIGH, "2.5")
|
||
# Disabled until further notice
|
||
# field(FLNK, "$(P)$(R)TMPump1-ControllerOffInv" )
|
||
field(VAL,"0")
|
||
}
|
||
|
||
record(calcout, "$(P)$(R)TMPump1-ControllerOffInv") {
|
||
field(INPA, "$(P)$(R)TMPump1-ControllerOff NPP MS" )
|
||
field(OUT, "$(P)$(R)PCF8574:56:REGISTER.B1 PP MS")
|
||
field(OOPT, "On Change")
|
||
field(CALC, "A?0:1")
|
||
}
|
||
|
||
record(bo, "$(P)$(R)TMPump1-MotorOn" ) {
|
||
field( ZNAM, "Off")
|
||
field( ONAM, "Pulse")
|
||
field( HIGH, "2.5")
|
||
field( FLNK, "$(P)$(R)TMPump1-MotorOnInv")
|
||
}
|
||
|
||
record(calcout, "$(P)$(R)TMPump1-MotorOnInv" ) {
|
||
field( INPA, "$(P)$(R)TMPump1-MotorOn NPP MS")
|
||
field( OUT, "$(P)$(R)PCF8574:56:REGISTER.B2 PP MS")
|
||
field( OOPT, "On Change")
|
||
field( CALC, "A?0:1" )
|
||
}
|
||
|
||
record(bo, "$(P)$(R)TMPump1-MotorOff") {
|
||
field( ZNAM, "Off")
|
||
field( ONAM, "Pulse")
|
||
field( HIGH, "2.5")
|
||
field( FLNK, "$(P)$(R)TMPump1-MotorOffInv")
|
||
field(VAL,"0")
|
||
}
|
||
|
||
record(calcout, "$(P)$(R)TMPump1-MotorOffInv") {
|
||
field( INPA, "$(P)$(R)TMPump1-MotorOff NPP MS")
|
||
field( OUT, "$(P)$(R)PCF8574:56:REGISTER.B3 PP MS")
|
||
field( OOPT, "On Change")
|
||
field( CALC, "A?0:1")
|
||
}
|
||
|
||
#############################
|
||
### TMP1 Controller inputs###
|
||
#############################
|
||
record(fanout, "$(P)$(R)PCF8574:56:REGISTER:READ:FNOUT"){
|
||
field(LNK1, "$(P)$(R)TMPump1-Power")
|
||
field(LNK2, "$(P)$(R)TMPump1-Emergency")
|
||
field(LNK3, "$(P)$(R)TMPump1-Acceleration")
|
||
field(LNK4, "$(P)$(R)TMPump1-NormalOperation")
|
||
}
|
||
record(bi , "$(P)$(R)TMPump1-Power" ) {
|
||
field(DESC," TMP1 – Alimentada 220V ")
|
||
field( INP, "$(P)$(R)PCF8574:56:REGISTER:READ.B4 NPP NMS")
|
||
field( ZNAM, "ON" )
|
||
field( ONAM, "OFF" )
|
||
}
|
||
record(bi , "$(P)$(R)TMPump1-Emergency") {
|
||
field(DESC," TMP1 – Falha ")
|
||
field( INP, "$(P)$(R)PCF8574:56:REGISTER:READ.B6 NPP NMS")
|
||
# field(VAL,"1")
|
||
field( ZNAM, "ON" )
|
||
field( ONAM, "OFF" )
|
||
field(ZSV,"MAJOR")
|
||
}
|
||
record(bi , "$(P)$(R)TMPump1-Acceleration") {
|
||
field(DESC," TMP1 – Motor em aceleração ")
|
||
field( INP, "$(P)$(R)PCF8574:56:REGISTER:READ.B5 NPP NMS")
|
||
field( ZNAM, "ON" )
|
||
field( ONAM, "OFF" )
|
||
field(ZSV,"MINOR")
|
||
}
|
||
|
||
record(bi , "$(P)$(R)TMPump1-NormalOperation" ) {
|
||
field(DESC," TMP1 – Operação Normal ")
|
||
field( INP, "$(P)$(R)PCF8574:56:REGISTER:READ.B7 NPP NMS")
|
||
field( ZNAM, "ON" )
|
||
field(ONAM, "OFF" )
|
||
field(OSV,"MINOR")
|
||
}
|
||
|
||
###############
|
||
###############
|
||
# REGISTER 57 #
|
||
###############
|
||
###############
|
||
|
||
##############################
|
||
### TMP2 Controller Inputs ###
|
||
##############################
|
||
record(fanout, "$(P)$(R)PCF8574:57:REGISTER:READ:FNOUT"){
|
||
field(LNK1, "$(P)$(R)TMPump2-Emergency")
|
||
field(LNK2, "$(P)$(R)TMPump2-Acceleration")
|
||
field(LNK3, "$(P)$(R)TTSystem-tzero")
|
||
field(LNK4, "$(P)$(R)Emergency-PhysButton")
|
||
}
|
||
record(bi , "$(P)$(R)TMPump2-Emergency") {
|
||
field(DESC," TMP2 – Falha ")
|
||
# field(INP, "$(P)$(R)PCF8574:57:REGISTER:READ.B0 NPP NMS")
|
||
field(VAL,"1")
|
||
field(ZNAM, "ON" )
|
||
field(ONAM, "OFF" )
|
||
field(ZSV,"MAJOR")
|
||
}
|
||
|
||
record(bi , "$(P)$(R)TMPump2-Acceleration") {
|
||
field(DESC," TMP2 – START until Normal ")
|
||
field( INP, "$(P)$(R)PCF8574:57:REGISTER:READ.B1 NPP NMS")
|
||
field( ZNAM, "ON" )
|
||
field( ONAM, "OFF" )
|
||
}
|
||
####################################
|
||
# TIMING TRIGGER ON/OFF #
|
||
####################################
|
||
record(bi , "$(P)$(R)TTSystem-tzero" ) {
|
||
field(DESC,"Trigger control 60s before shot")
|
||
field(INP, "$(P)$(R)PCF8574:57:REGISTER:READ.B7")
|
||
# field(VAL,"1")
|
||
field(ZNAM, "OFF" )
|
||
field(ONAM, "ON" )
|
||
}
|
||
|
||
###############################
|
||
### TMP2 Controller Outputs ###
|
||
###############################
|
||
record(bo, "$(P)$(R)TMPump2-Motor" ) {
|
||
field(DESC," Motor On/Off ")
|
||
# record(bo, "$(P)$(R)TMP2MotorOnOff" ) {
|
||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B2 PP MS")
|
||
field( ZNAM, "ON")
|
||
field( ONAM, "OFF")
|
||
}
|
||
|
||
##############################
|
||
# BUZZER ON/OFF #
|
||
##############################
|
||
record(bo, "$(P)$(R)Buzzer" ) {
|
||
field(DESC," Lab Buzzer ")
|
||
field(ZNAM, "Off" )
|
||
field(ONAM, "Pulse" )
|
||
field(HIGH, "2.5")
|
||
field(FLNK, "$(P)$(R)BuzzerInv" )
|
||
field(VAL, "0")
|
||
}
|
||
record(calcout, "$(P)$(R)BuzzerInv" ) {
|
||
field(INPA, "$(P)$(R)Buzzer NPP MS" )
|
||
field(OUT, "$(P)$(R)PCF8574:57:REGISTER.B3 PP MS" )
|
||
field(OOPT, "On Change" )
|
||
field(CALC, "A?0:1" )
|
||
}
|
||
|
||
##############################
|
||
# EMERGENCY MODE #
|
||
##############################
|
||
record(bi, "$(P)$(R)Emergency-PhysButton" ) {
|
||
field(DESC,"External Physical Emergency Button")
|
||
field(INP, "$(P)$(R)PCF8574:57:REGISTER:READ.B4 NPP NMS")
|
||
field(ZNAM, "ON")
|
||
field(ONAM, "OFF" )
|
||
field(FLNK, "$(P)$(R)Emergency" )
|
||
}
|
||
record(bo, "$(P)$(R)Emergency-UserButton" ) {
|
||
field(DESC,"Soft User Emergency Button")
|
||
field(ZNAM, "OFF" )
|
||
field(ONAM, "ON")
|
||
field(FLNK, "$(P)$(R)Emergency" )
|
||
}
|
||
record(calc, "$(P)$(R)Emergency" ) {
|
||
field(DESC, "Emergency State")
|
||
field(INPA, "$(P)$(R)Emergency-PhysButton.RVAL NPP" )
|
||
field(INPB, "$(P)$(R)Emergency-UserButton.RVAL NPP" )
|
||
field(CALC, "A || B" ) # ! Not
|
||
}
|
||
|
||
############
|
||
# NOT USED #
|
||
############
|
||
#$(P)$(R)PCF8574:57:REGISTER:READ.B5
|
||
#$(P)$(R)PCF8574:57:REGISTER:READ.B6
|
||
|
||
|
||
###############
|
||
###############
|
||
# REGISTER 60 #
|
||
###############
|
||
###############
|
||
|
||
###################################
|
||
# ROTARY1 PUMP Relay 5 NC #
|
||
###################################
|
||
record( bo, "$(P)$(R)RPump1-Motor" ) {
|
||
field(DESC,"Power to Rotatory Pump 1. Relay 5")
|
||
field(OUT, "$(P)$(R)PCF8574:60:REGISTER.B0 PP" )
|
||
field(ZNAM, "Off" )
|
||
field(ONAM, "On" )
|
||
field(VAL,"1")
|
||
field(ZSV,"MINOR")
|
||
}
|
||
|
||
####################################
|
||
# ROTARY1 VALVE Relay 4 NC #
|
||
####################################
|
||
record( bo, "$(P)$(R)RPump1-Valve" ) {
|
||
field(DESC,"Abre a valvula da bomba rot. Relay 4")
|
||
field(OUT, "$(P)$(R)PCF8574:60:REGISTER.B1 PP" )
|
||
field(ZNAM, "Closed" )
|
||
field(ONAM, "Open" )
|
||
field(VAL,"1")
|
||
}
|
||
|
||
#############################
|
||
# ROTARY2 PUMP NO LONGUER USED (RESERVED) #
|
||
#############################
|
||
record( bo, "$(P)$(R)RPump2-Motor" ) {
|
||
field(DESC,"Power On Rotatory Pump 2")
|
||
# field(OUT, "$(P)$(R)PCF8574:60:REGISTER.B2 PP" )
|
||
field(ZNAM, "Off" )
|
||
field(ONAM, "On" )
|
||
field(VAL,"1")
|
||
field(ZSV,"MINOR")
|
||
}
|
||
|
||
#############################
|
||
# ROTARY2 VALVE NO LONGUER USED (RESERVED) #
|
||
#############################
|
||
record( bo, "$(P)$(R)RPump2-Valve" ) {
|
||
field(DESC," Abre a valvula da bomba rotatoria 2 ")
|
||
# field(OUT,"$(P)$(R)PCF8574:60:REGISTER.B3 PP" )
|
||
field(ZNAM,"Closed" )
|
||
field(ONAM,"Open" )
|
||
field(VAL,"1")
|
||
}
|
||
|
||
################################
|
||
# FILAMENT ON/OFF #
|
||
################################
|
||
record(bo, "$(P)$(R)VVessel-Filament" ) {
|
||
field(DESC,"Vacuum Vessel Filament power")
|
||
# record(bo, "$(P)$(R)FilamentOnOff" ) {
|
||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B4 PP" )
|
||
field( ZNAM, "On" )
|
||
field( ONAM, "Off" )
|
||
field(VAL,"1")
|
||
field(PINI,"YES")
|
||
}
|
||
|
||
##############################
|
||
# LIGHTS ON/OFF #
|
||
##############################
|
||
record(bo, "$(P)$(R)Lab-WarningLight" ) {
|
||
field(DESC," Luzes de sinalização, 220V ")
|
||
# record(bo, "$(P)$(R)LightsOnOff" ) {
|
||
field(OUT, "$(P)$(R)PCF8574:60:REGISTER.B5 PP" )
|
||
field(ZNAM, "On" )
|
||
field(ONAM, "Off" )
|
||
field(VAL,"1")
|
||
}
|
||
|
||
############
|
||
# NOT USED #
|
||
############
|
||
#$(P)$(R)PCF8574:60:REGISTER:READ.B6
|
||
|
||
##############################
|
||
# TOR CLEAN CONTACTOR ON/OFF #
|
||
##############################
|
||
record(bo, "$(P)$(R)Clean-TorContactor" ) {
|
||
# field(DESC," Contactor 220V do transformador para a fonte de campo toroidal das descargas de limpeza (500 A) ")
|
||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B7 PP" )
|
||
field( ZNAM, "On" )
|
||
field( ONAM, "Off" )
|
||
field(VAL,"1")
|
||
}
|
||
|
||
###############
|
||
###############
|
||
# REGISTER 61 #
|
||
###############
|
||
###############
|
||
|
||
############################
|
||
# TOR CLEAN BREAKER ON/OFF #
|
||
############################
|
||
record(bo, "$(P)$(R)Clean-TorPneuBreaker" ) {
|
||
## field(DESC," Interruptor de ar comprimido do transformador para a fonte de campo toroidal das descargas de limpeza (500 A)")
|
||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B0 PP" )
|
||
field( ZNAM, "On" )
|
||
field( ONAM, "Off" )
|
||
field(VAL,"1")
|
||
}
|
||
|
||
record(bo, "$(P)$(R)Shot-TorPSDisable" ) {
|
||
# field(DESC," É desligado na emergência e em qualquer estado que não seja Process ou Wait Shot.")
|
||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B1 PP" )
|
||
field( ZNAM, "Off" )
|
||
field( ONAM, "On" )
|
||
field(VAL,"1")
|
||
}
|
||
|
||
record(bo, "$(P)$(R)Shot-TorPSTrigger" ) {
|
||
field(DESC," Trigger da FRAEP")
|
||
field( ZNAM, "Off" )
|
||
field( ONAM, "Pulse" )
|
||
field( HIGH, "2.5")
|
||
field( FLNK, "$(P)$(R)Shot-TorPSTriggerInv" )
|
||
field(VAL,"0")
|
||
}
|
||
record(calcout, "$(P)$(R)Shot-TorPSTriggerInv" ) {
|
||
# field(DESC," $(R)")
|
||
field( INPA, "$(P)$(R)ToroidalShotTriggerOnOff NPP MS" )
|
||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B2 PP MS" )
|
||
field( OOPT, "On Change" )
|
||
field( CALC, "A?0:1" )
|
||
}
|
||
############################################################
|
||
|
||
#######################################
|
||
# CAP BANK CHARGE ON/OFF #
|
||
#######################################
|
||
record(bo, "$(P)$(R)CapBank-Charge" ) {
|
||
## field(DESC," Contactor 220V do circuito de carga do banco de condensadores p/ SHOT (ELCO) ")
|
||
#record(bo, "$(P)$(R)CapBankChargeOnOff" ) {
|
||
field(OUT, "$(P)$(R)PCF8574:61:REGISTER.B3 PP" )
|
||
field(ZNAM, "On" )
|
||
field(ONAM, "Off" )
|
||
field(VAL,"1")
|
||
}
|
||
|
||
########################################
|
||
# PRIMARY CLEAN CONTACTOR ON/OFF #
|
||
########################################
|
||
record(bo, "$(P)$(R)Clean-PrimContactor" ) {
|
||
# field(DESC," Contactor 220V do para o primário das descargas de limpeza ")
|
||
# record(bo, "$(P)$(R)PrimaryCleanContactorOnOff" ) {
|
||
field(OUT, "$(P)$(R)PCF8574:61:REGISTER.B4 PP MS" )
|
||
field(ZNAM, "On" )
|
||
field(ONAM, "Off" )
|
||
field(VAL,"1")
|
||
}
|
||
|
||
####################################
|
||
### PRIMARY CLEAN BREAKER ON/OFF ###
|
||
####################################
|
||
record(bo, "$(P)$(R)Clean-PrimPneuBreaker"){
|
||
#record(bo, "$(P)$(R)PrimaryCleanBreakerOnOff"){
|
||
field( DESC, "Primary Cleaning OnOff")
|
||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B5 PP" )
|
||
field( ZNAM, "On")
|
||
field( ONAM, "Off")
|
||
field(VAL,"1")
|
||
}
|
||
|
||
##################################
|
||
# GIS VALVES ON/OFF #
|
||
##################################
|
||
record(bo, "$(P)$(R)GasIS-Valves" ) {
|
||
# field(DESC," 2 válvulas pneumáticas de corte do sistema de injecção de H/D/Ne/He no TOK, 24V out = deixa passar")
|
||
# record(bo, "$(P)$(R)GISValvesOnOff" ) {
|
||
field( OUT, "$(P)$(R)SEEED4RELAY:17:REGISTER.B0 PP" )
|
||
field( ZNAM, "OFF" )
|
||
field( ONAM, "ON" )
|
||
field(VAL,"0")
|
||
}
|
||
|
||
##########################################
|
||
# CAP BANK DISCHARGE ON/OFF #
|
||
##########################################
|
||
record(bo, "$(P)$(R)CapBank-Discharge" ) {
|
||
field(DESC," Liga o circuito de descarga do ELCO ")
|
||
# record(bo, "$(P)$(R)CapBankDischargeOnOff" ) {
|
||
field(OUT, "$(P)$(R)PCF8574:61:REGISTER.B7 PP" )
|
||
field(ZNAM, "On" )
|
||
field(ONAM, "Off" )
|
||
field(VAL,"1")
|
||
}
|
||
|
||
#record(bo,"$(P)$(R)Primary-PressureCondition"){
|
||
# field(ZNAM, "OFF" )
|
||
# field(ONAM, "ON" )
|
||
# field(VAL,"0")
|
||
#}
|
||
|
||
record(ai,"$(P)$(R)TMPump2-Speed"){
|
||
# field(DESC," ADC Pump speed 0-10V ")
|
||
#record(ai,"$(P)$(R)Turbo2_Speed"){
|
||
field(PREC,"3")
|
||
field(EGU,"RPM")
|
||
field(VAL,"0")
|
||
}
|
||
|
||
#######################
|
||
###TMP1 Manual Valve###
|
||
#######################
|
||
record(bo, "$(P)$(R)TMPump1-ManualValve"){
|
||
# field(DESC," $(R)")
|
||
#record(bo, "$(P)$(R)TMPManualValve"){
|
||
info(autosaveFields, "VAL")
|
||
field( DESC, "State of manual valve")
|
||
field( ZNAM, "Closed")
|
||
field( ONAM, "Open")
|
||
}
|