Moved pfeiffer sensors to central IOC. MSS fields where added
This commit is contained in:
@@ -27,7 +27,8 @@ record(bo, "$(P)$(R)TMPump1-ControllerOn" ) {
|
||||
field(ZNAM, "Off" )
|
||||
field(ONAM, "Pulse" )
|
||||
field(HIGH, "2.5")
|
||||
field(FLNK, "$(P)$(R)TMPump1-ControllerOnInv" )
|
||||
# Disabled until further notice
|
||||
# field(FLNK, "$(P)$(R)TMPump1-ControllerOnInv" )
|
||||
field(VAL,"0")
|
||||
}
|
||||
record(calcout, "$(P)$(R)TMPump1-ControllerOnInv") {
|
||||
@@ -43,7 +44,8 @@ record(bo, "$(P)$(R)TMPump1-ControllerOff" ) {
|
||||
field(ZNAM, "Off" )
|
||||
field(ONAM, "Pulse" )
|
||||
field(HIGH, "2.5")
|
||||
field(FLNK, "$(P)$(R)TMPump1-ControllerOffInv" )
|
||||
# Disabled until further notice
|
||||
# field(FLNK, "$(P)$(R)TMPump1-ControllerOffInv" )
|
||||
field(VAL,"0")
|
||||
}
|
||||
|
||||
|
||||
@@ -94,6 +94,8 @@ record(ai, "$(P)$(R)Shot-TorPSCurrentImage" ) {
|
||||
field(DTYP, "Raw Soft Channel" )
|
||||
field(INP, "$(P)$(R)PCF8591:72:BYTE2_CH3 PP NMS")
|
||||
field(SCAN, ".2 second")
|
||||
#Scan Disable Input Link Value
|
||||
field(DISA, "1")
|
||||
field(ASLO, "39.215686275" )
|
||||
field(AOFF, "0.0" )
|
||||
field(EGU, "A" )
|
||||
|
||||
@@ -1,121 +1,126 @@
|
||||
# vim: sta:et:sw=4:ts=4:sts=4
|
||||
# 8/5/2021 Only sensor 2 is working. Running with dspIC
|
||||
# 20/9/2021 sensors 1,2,3 are working. Running with dspIC
|
||||
# 20/9/2021 sensors 1,2,3 are working. Running with tty USB
|
||||
record (longin, "$(P)$(R)P001:M")
|
||||
{
|
||||
field (DESC, "getPressure001 $(bus)")
|
||||
field (DTYP, "stream")
|
||||
field (INP, "@pfeiffer.proto getPressure001($(P)$(R)P001:E) $(bus)")
|
||||
# field (SCAN, "I/O Intr")
|
||||
field (SCAN, "1 second")
|
||||
field (FLNK, "$(P)$(R)TMPump1-PressureAdmission")
|
||||
field (DESC, "getPressure001 $(bus)")
|
||||
field (DTYP, "stream")
|
||||
field (INP, "@pfeiffer.proto getPressure001($(P)$(R)P001:E) $(bus)")
|
||||
# field (SCAN, "I/O Intr")
|
||||
field (SCAN, "1 second")
|
||||
field(PHAS, "1")
|
||||
field (FLNK, "$(P)$(R)TMPump1-PressureAdmission")
|
||||
}
|
||||
record (longin, "$(P)$(R)P001:E")
|
||||
{
|
||||
field (DESC, "Pressure001 exponent $(bus)")
|
||||
field (DESC, "Pressure001 exponent $(bus)")
|
||||
}
|
||||
record (calc, "$(P)$(R)TMPump1-PressureAdmission")
|
||||
{
|
||||
field(DESC, "ISTTOK:central:TMPump1-PressureAdmission")
|
||||
field(INPA, "$(P)$(R)P001:M")
|
||||
field(INPB, "$(P)$(R)P001:E")
|
||||
field(CALC, "(A*0.001)* 10.0**(B-20)")
|
||||
field(PREC, "3")
|
||||
field(EGU, "mBar")
|
||||
field(HIHI,"1.0e-2")
|
||||
field(HIGH,"1.0e-3")
|
||||
field(DESC, "ISTTOK:central:TMPump1-PressureAdmission")
|
||||
# Maximize Status and Severity, MSS propagate all alarms
|
||||
field(INPA, "$(P)$(R)P001:M MSS")
|
||||
field(INPB, "$(P)$(R)P001:E")
|
||||
field(CALC, "(A*0.001)* 10.0**(B-20)")
|
||||
field(PREC, "3")
|
||||
field(EGU, "mBar")
|
||||
field(HIHI,"1.0e-2")
|
||||
field(HIGH,"1.0e-3")
|
||||
# field(LOW, "20.0")
|
||||
# field(LOLO,"0.0")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
# field(LSV, "MINOR")
|
||||
# field(LLSV,"MAJOR")
|
||||
# field(LLSV,"MAJOR")
|
||||
}
|
||||
# out "0020074002=?107";
|
||||
record (longin, "$(P)$(R)P002:M")
|
||||
{
|
||||
field (DESC, "getPressure002 $(bus)")
|
||||
field (DTYP, "stream")
|
||||
field (INP, "@pfeiffer.proto getPressure002($(P)$(R)P002:E) $(bus)")
|
||||
# field (SCAN, "I/O Intr")
|
||||
field (SCAN, "1 second")
|
||||
field (FLNK, "$(P)$(R)RPump1-Pressure")
|
||||
field (DESC, "getPressure002 $(bus)")
|
||||
field (DTYP, "stream")
|
||||
field (INP, "@pfeiffer.proto getPressure002($(P)$(R)P002:E) $(bus)")
|
||||
# field (SCAN, "I/O Intr")
|
||||
field (SCAN, "1 second")
|
||||
field(PHAS, "0")
|
||||
field (FLNK, "$(P)$(R)RPump1-Pressure")
|
||||
}
|
||||
record (longin, "$(P)$(R)P002:E")
|
||||
{
|
||||
field (DESC, "Pressure002 exponent $(bus)")
|
||||
field (DESC, "Pressure002 exponent $(bus)")
|
||||
}
|
||||
record (calc, "$(P)$(R)RPump1-Pressure")
|
||||
{
|
||||
field (DESC, "ISTTOK:central:RPump1-Pressure")
|
||||
field(INPA, "$(P)$(R)P002:M")
|
||||
field(INPB, "$(P)$(R)P002:E")
|
||||
field(CALC, "(A*0.001)*10.0**(B-20)")
|
||||
field(PREC, "3")
|
||||
field(EGU, "mBar")
|
||||
field(HIHI,"1.0e-1")
|
||||
field(HIGH,"5.0e-2")
|
||||
field (DESC, "ISTTOK:central:RPump1-Pressure")
|
||||
field(INPA, "$(P)$(R)P002:M MSS")
|
||||
field(INPB, "$(P)$(R)P002:E")
|
||||
field(CALC, "(A*0.001)*10.0**(B-20)")
|
||||
field(PREC, "3")
|
||||
field(EGU, "mBar")
|
||||
field(HIHI,"1.0e-1")
|
||||
field(HIGH,"5.0e-2")
|
||||
# field(LOW, "20.0")
|
||||
# field(LOLO,"0.0")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
# field(LSV, "MINOR")
|
||||
# field(LLSV,"MAJOR")
|
||||
# field(LLSV,"MAJOR")
|
||||
}
|
||||
|
||||
# out "0030074002=?108";
|
||||
record (longin, "$(P)$(R)P003:M")
|
||||
{
|
||||
field (DESC, "getPressure003 Mantissa $(bus)")
|
||||
field (DTYP, "stream")
|
||||
field (INP, "@pfeiffer.proto getPressure003($(P)$(R)P003:E) $(bus)")
|
||||
field (SCAN, "1 second")
|
||||
# field (SCAN, "I/O Intr")
|
||||
field (FLNK, "$(P)$(R)VVessel-Pressure")
|
||||
field (DESC, "getPressure003 Mantissa $(bus)")
|
||||
field (DTYP, "stream")
|
||||
field (INP, "@pfeiffer.proto getPressure003($(P)$(R)P003:E) $(bus)")
|
||||
field (SCAN, "1 second")
|
||||
field(PHAS, "2")
|
||||
# field (SCAN, "I/O Intr")
|
||||
field (FLNK, "$(P)$(R)VVessel-Pressure")
|
||||
}
|
||||
|
||||
record (longin, "$(P)$(R)P003:E")
|
||||
{
|
||||
field (DESC, "Pressure003 Exponent $(bus)")
|
||||
field (DESC, "Pressure003 Exponent $(bus)")
|
||||
}
|
||||
record (calc, "$(P)$(R)VVessel-Pressure")
|
||||
{
|
||||
field (DESC, "ISTTOK:central:VVessel-Pressure")
|
||||
field(INPA, "$(P)$(R)P003:M")
|
||||
field(INPB, "$(P)$(R)P003:E")
|
||||
field(CALC, "(A*0.001)*10.0**(B-20)")
|
||||
field(PREC, "3")
|
||||
field(EGU, "mBar")
|
||||
field(HIHI,"1.0e-1")
|
||||
field(HIGH,"1.0e-2")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
field (DESC, "ISTTOK:central:VVessel-Pressure")
|
||||
field(INPA, "$(P)$(R)P003:M MSS")
|
||||
field(INPB, "$(P)$(R)P003:E")
|
||||
field(CALC, "(A*0.001)*10.0**(B-20)")
|
||||
field(PREC, "3")
|
||||
field(EGU, "mBar")
|
||||
field(HIHI,"1.0e-1")
|
||||
field(HIGH,"1.0e-2")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
}
|
||||
|
||||
# out "0040074002=?109";
|
||||
# NOT connected 26/10/2021
|
||||
record (longin, "$(P)$(R)P004:M")
|
||||
{
|
||||
field (DESC, "getPressure004 Mantissa $(bus)")
|
||||
field (DTYP, "stream")
|
||||
field (INP, "@pfeiffer.proto getPressure004($(P)$(R)P004:E) $(bus)")
|
||||
# field (SCAN, "1 second")
|
||||
# field (SCAN, "I/O Intr")
|
||||
field (FLNK, "$(P)$(R)RPump2-Pressure")
|
||||
field (DESC, "getPressure004 Mantissa $(bus)")
|
||||
field (DTYP, "stream")
|
||||
field (INP, "@pfeiffer.proto getPressure004($(P)$(R)P004:E) $(bus)")
|
||||
# field (SCAN, "1 second")
|
||||
# field (SCAN, "I/O Intr")
|
||||
field (FLNK, "$(P)$(R)RPump2-Pressure")
|
||||
}
|
||||
record (longin, "$(P)$(R)P004:E")
|
||||
{
|
||||
field (DESC, "Pressure004 Exponent $(bus)")
|
||||
field (DESC, "Pressure004 Exponent $(bus)")
|
||||
}
|
||||
|
||||
record (calc, "$(P)$(R)RPump2-Pressure")
|
||||
{
|
||||
field(DESC, "ISTTOK:central:RPump2-Pressure")
|
||||
field(INPA, "$(P)$(R)P004:M")
|
||||
field(INPB, "$(P)$(R)P004:E")
|
||||
field(CALC, "(A*0.001)* 10.0**(B-20)")
|
||||
field(PREC, "3")
|
||||
field(EGU, "mBar")
|
||||
field(DESC, "ISTTOK:central:RPump2-Pressure")
|
||||
field(INPA, "$(P)$(R)P004:M MSS")
|
||||
field(INPB, "$(P)$(R)P004:E")
|
||||
field(CALC, "(A*0.001)* 10.0**(B-20)")
|
||||
field(PREC, "3")
|
||||
field(EGU, "mBar")
|
||||
# field(HIHI,"1.0e-1")
|
||||
# field(HIGH,"5.0e-3")
|
||||
# field(LOW, "20.0")
|
||||
@@ -123,13 +128,13 @@ record (calc, "$(P)$(R)RPump2-Pressure")
|
||||
# field(HHSV,"MAJOR")
|
||||
# field(HSV, "MINOR")
|
||||
# field(LSV, "MINOR")
|
||||
# field(LLSV,"MAJOR")
|
||||
# field(LLSV,"MAJOR")
|
||||
}
|
||||
|
||||
record(stringout,"$(P)$(R)RS485Debug") {
|
||||
field(DESC, "")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@pfeiffer.proto debug $(bus)")
|
||||
field(VAL,"")
|
||||
field(DESC, "")
|
||||
field(DTYP, "stream")
|
||||
field(OUT, "@pfeiffer.proto debug $(bus)")
|
||||
field(VAL,"")
|
||||
}
|
||||
|
||||
|
||||
@@ -1,3 +1,4 @@
|
||||
# vim: sta:et:sw=4:ts=4:sts=4
|
||||
#
|
||||
# Project : ISTTOK slow Control
|
||||
#
|
||||
@@ -13,257 +14,267 @@
|
||||
##
|
||||
|
||||
record(mbbi, "$(P)$(R)OPSTATE") {
|
||||
field(DESC, "Multiple Pulse Sequence State")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(SXVL, "6")
|
||||
field(SVVL, "7")
|
||||
field(ZRST, "Stopped")
|
||||
field(ONST, "Starting")
|
||||
field(TWST, "Idle")
|
||||
field(THST, "Clean")
|
||||
field(FRST, "WaitShot")
|
||||
field(FVST, "Stopping")
|
||||
field(SXST, "Emergency")
|
||||
field(SVST, "UPSEmergency")
|
||||
field(VAL, "0")
|
||||
field(DESC, "Multiple Pulse Sequence State")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(SXVL, "6")
|
||||
field(SVVL, "7")
|
||||
field(ZRST, "Stopped")
|
||||
field(ONST, "Starting")
|
||||
field(TWST, "Idle")
|
||||
field(THST, "Clean")
|
||||
field(FRST, "WaitShot")
|
||||
field(FVST, "Stopping")
|
||||
field(SXST, "Emergency")
|
||||
field(SVST, "UPSEmergency")
|
||||
field(VAL, "0")
|
||||
field(FLNK, "$(P)$(R)OPCALCSTATE")
|
||||
#field(PINI, "YES")
|
||||
}
|
||||
record(mbbo, "$(P)$(R)LASTOPSTATE") {
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Pulse Sequence Last Saved State")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(SXVL, "6")
|
||||
field(SVVL, "7")
|
||||
field(ZRST, "Stopped")
|
||||
field(ONST, "Starting")
|
||||
field(TWST, "Idle")
|
||||
field(THST, "Clean")
|
||||
field(FRST, "WaitShot")
|
||||
field(FVST, "Stopping")
|
||||
field(SXST, "Emergency")
|
||||
field(SVST, "UPSEmergency")
|
||||
# field(VAL, "0")
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Pulse Sequence Last Saved State")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(SXVL, "6")
|
||||
field(SVVL, "7")
|
||||
field(ZRST, "Stopped")
|
||||
field(ONST, "Starting")
|
||||
field(TWST, "Idle")
|
||||
field(THST, "Clean")
|
||||
field(FRST, "WaitShot")
|
||||
field(FVST, "Stopping")
|
||||
field(SXST, "Emergency")
|
||||
field(SVST, "UPSEmergency")
|
||||
field(PINI, "YES")
|
||||
# field(VAL, "0")
|
||||
}
|
||||
|
||||
# record for bit leds
|
||||
record(calc, "$(P)$(R)OPCALCSTATE") {
|
||||
field(DESC, "Pulse Calculated State")
|
||||
field(CALC,"2^A")
|
||||
field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)OPSTATE.VAL PP NMS")
|
||||
field(DESC, "Pulse Calculated State")
|
||||
field(CALC,"2^A")
|
||||
#field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)OPSTATE.VAL NPP NMS")
|
||||
}
|
||||
|
||||
record(calc, "$(P)$(R)STARTCALCSTATE") {
|
||||
field(DESC, "Start Calculated State")
|
||||
field(CALC,"2^A")
|
||||
field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)STARTINGSTATE.VAL PP NMS")
|
||||
field(DESC, "Start Calculated State")
|
||||
field(CALC,"2^A")
|
||||
field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)STARTINGSTATE.VAL PP NMS")
|
||||
}
|
||||
|
||||
record(calc, "$(P)$(R)STOPPINGCALCSTATE") {
|
||||
field(DESC, "Stop Calculated State")
|
||||
field(CALC,"2^A")
|
||||
field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)STOPPINGSTATE.VAL PP NMS")
|
||||
field(DESC, "Stop Calculated State")
|
||||
field(CALC,"2^A")
|
||||
field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)STOPPINGSTATE.VAL PP NMS")
|
||||
}
|
||||
|
||||
record(calc, "$(P)$(R)CLEANCALCSTATE") {
|
||||
field(DESC, "Clean Automatic Calculated State")
|
||||
field(CALC,"(2^(A+1))-1")
|
||||
field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)CLEANINGSTATE.VAL PP NMS")
|
||||
field(DESC, "Clean Automatic Calculated State")
|
||||
field(CALC,"(2^(A+1))-1")
|
||||
field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)CLEANINGSTATE.VAL PP NMS")
|
||||
}
|
||||
|
||||
|
||||
record(calc, "$(P)$(R)WSHOTCALCSTATE") {
|
||||
field(DESC, "WaitShot Calculated State")
|
||||
field(CALC,"2^A")
|
||||
field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)WSHOTINGSTATE.VAL PP NMS")
|
||||
field(DESC, "WaitShot Calculated State")
|
||||
field(CALC,"2^A")
|
||||
field(SCAN,"1 second")
|
||||
field(INPA,"$(P)$(R)WSHOTINGSTATE.VAL PP NMS")
|
||||
}
|
||||
|
||||
#record(ai, "$(P)$(R)Temperature_0") {
|
||||
# field(DESC, "ISTTOK Temperature 0 Calculated")
|
||||
# field(EGU, "C")
|
||||
# field(SCAN,"1 second")
|
||||
# field(DESC, "ISTTOK Temperature 0 Calculated")
|
||||
# field(EGU, "C")
|
||||
# field(SCAN,"1 second")
|
||||
#}
|
||||
|
||||
record(bo, "$(P)$(R)UPS-OnBattery") {
|
||||
info(autosaveFields, "VAL STAT")
|
||||
field(DESC, "Main APC UPS On Battery status")
|
||||
field(VAL, "0")
|
||||
field(ZNAM, "OFF")
|
||||
field(ONAM, "ON")
|
||||
info(autosaveFields, "VAL STAT")
|
||||
field(DESC, "Main APC UPS On Battery status")
|
||||
field(VAL, "0")
|
||||
field(ZNAM, "OFF")
|
||||
field(ONAM, "ON")
|
||||
field(OSV, "MAJOR")
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)UPS-Shutdown") {
|
||||
info(autosaveFields, "VAL STAT")
|
||||
field(DESC, "Main APC UPS Shutdown request")
|
||||
# field(VAL, "0")
|
||||
field(ZNAM, "OFF")
|
||||
field(ONAM, "ON")
|
||||
info(autosaveFields, "VAL STAT")
|
||||
field(DESC, "Main APC UPS Shutdown request")
|
||||
# field(VAL, "0")
|
||||
field(ZNAM, "OFF")
|
||||
field(ONAM, "ON")
|
||||
field(OSV, "MAJOR")
|
||||
field(PINI, "YES")
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)OPREQ") {
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Pulse Sequence Start/Stop")
|
||||
# field(VAL, "0")
|
||||
field(ZNAM, "STOP")
|
||||
field(ONAM, "START")
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Pulse Sequence Start/Stop")
|
||||
# field(VAL, "0")
|
||||
field(PINI, "YES")
|
||||
field(ZNAM, "STOP")
|
||||
field(ONAM, "START")
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)CLEANINGMANMODE") {
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Cleaning Manual/Auto")
|
||||
info(autosaveFields, "VAL")
|
||||
# field(VAL, "1")
|
||||
field(ZNAM, "M")
|
||||
field(ONAM, "A")
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Cleaning Manual/Auto")
|
||||
info(autosaveFields, "VAL")
|
||||
# field(VAL, "1")
|
||||
field(ZNAM, "M")
|
||||
field(ONAM, "A")
|
||||
}
|
||||
|
||||
|
||||
record(bo, "$(P)$(R)FSTriggerStart") {
|
||||
field(DESC, "FireSignal Trigger Start")
|
||||
field(VAL, "0")
|
||||
field(ZNAM, "STOP")
|
||||
field(ONAM, "START")
|
||||
field(DESC, "FireSignal Trigger Start")
|
||||
field(VAL, "0")
|
||||
field(PINI, "YES")
|
||||
field(ZNAM, "STOP")
|
||||
field(ONAM, "START")
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)PROCESS-MODE") {
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Plasma Process Mode")
|
||||
#field(VAL, "0")
|
||||
field(ZNAM, "CLEAN")
|
||||
field(ONAM, "SHOT")
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Plasma Process Mode")
|
||||
#field(VAL, "0")
|
||||
field(PINI, "YES")
|
||||
field(ZNAM, "CLEAN")
|
||||
field(ONAM, "SHOT")
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)PROCESS-REQ") {
|
||||
field(DESC, "Plasma Process sub-states Start/Stop")
|
||||
field(VAL, "0")
|
||||
field(ZNAM, "STOP")
|
||||
field(ONAM, "START")
|
||||
field(DESC, "Plasma Process sub-states Start/Stop")
|
||||
field(VAL, "0")
|
||||
field(PINI, "YES")
|
||||
field(ZNAM, "STOP")
|
||||
field(ONAM, "START")
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)AUTHORISATION") {
|
||||
field(DESC, "Pulse Sequence Authorisation Start/Abort")
|
||||
field(ZNAM, "ABORT")
|
||||
field(ONAM, "START")
|
||||
field(VAL, "0")
|
||||
field(DESC, "Pulse Sequence Authorisation Start/Abort")
|
||||
field(ZNAM, "ABORT")
|
||||
field(ONAM, "START")
|
||||
field(VAL, "0")
|
||||
}
|
||||
|
||||
record(longout, "$(P)$(R)PULSE-NUMBER") {
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Pulse Number")
|
||||
info(autosaveFields, "VAL")
|
||||
field(DESC, "Pulse Number")
|
||||
field(PINI, "YES")
|
||||
}
|
||||
|
||||
record(calc, "$(P)$(R)COUNTDOWN") {
|
||||
field(DESC, "Countdown Increment")
|
||||
field(INPA,"$(P)$(R)COUNTDOWN")
|
||||
field(SCAN,"Passive")
|
||||
field(CALC,"A+1")
|
||||
field(VAL, "160")
|
||||
field(DESC, "Countdown Increment")
|
||||
field(INPA,"$(P)$(R)COUNTDOWN")
|
||||
field(SCAN,"Passive")
|
||||
field(CALC,"A+1")
|
||||
field(VAL, "160")
|
||||
}
|
||||
|
||||
record(calc, "$(P)$(R)COUNTER") {
|
||||
field(DESC, "0.1 s counter")
|
||||
field(INPA, "$(P)$(R)COUNTER")
|
||||
field(SCAN, ".1 second")
|
||||
field(CALC, "A + .1")
|
||||
field(DESC, "0.1 s counter")
|
||||
field(INPA, "$(P)$(R)COUNTER")
|
||||
field(SCAN, ".1 second")
|
||||
field(CALC, "A + .1")
|
||||
}
|
||||
|
||||
record(stringin, "$(P)$(R)CurrentTime") {
|
||||
field(DESC, "Current Date and Time of the IOC")
|
||||
field(SCAN, "1 second")
|
||||
field(DTYP, "Soft Timestamp")
|
||||
field(PINI, "YES")
|
||||
field(INP, "@%d/%m/%Y %H:%M:%S")
|
||||
field(DESC, "Current Date and Time of the IOC")
|
||||
field(SCAN, "1 second")
|
||||
field(DTYP, "Soft Timestamp")
|
||||
#field(PINI, "YES")
|
||||
field(INP, "@%d/%m/%Y %H:%M:%S")
|
||||
}
|
||||
|
||||
record(stringout, "$(P)$(R)TraceMessage") {
|
||||
field(DESC, "Trace Message from IOC")
|
||||
field(VAL, "Trace mode ON")
|
||||
field(DESC, "Trace Message from IOC")
|
||||
field(VAL, "Trace mode ON")
|
||||
}
|
||||
|
||||
record(stringout, "$(P)$(R)LogMessage") {
|
||||
field(DESC, "Log Message ")
|
||||
# field(VAL, "Trace mode ON")
|
||||
field(DESC, "Log Message ")
|
||||
# field(VAL, "Trace mode ON")
|
||||
}
|
||||
|
||||
record(mbbi, "$(P)$(R)STARTINGSTATE") {
|
||||
field(DESC, "Starting State Sequence")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(ZRST, "NonStarting")
|
||||
field(ONST, "Starting1")
|
||||
field(TWST, "WaitManV")
|
||||
field(THST, "WaitPress")
|
||||
field(FRST, "WaitTMP")
|
||||
field(FVST, "StartEnd")
|
||||
field(VAL, "0")
|
||||
field(DESC, "Starting State Sequence")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(ZRST, "NonStarting")
|
||||
field(ONST, "Starting1")
|
||||
field(TWST, "WaitManV")
|
||||
field(THST, "WaitPress")
|
||||
field(FRST, "WaitTMP")
|
||||
field(FVST, "StartEnd")
|
||||
field(VAL, "0")
|
||||
}
|
||||
|
||||
record(mbbi, "$(P)$(R)CLEANINGSTATE") {
|
||||
field(DESC, "Cleaning State Sequence")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(ZRST, "NonCleaning")
|
||||
field(ONST, "Cleaning1")
|
||||
field(TWST, "Cleaning2")
|
||||
field(THST, "Cleaning3")
|
||||
field(FRST, "Cleaning4")
|
||||
field(FVST, "Cleaning5")
|
||||
field(VAL, "0")
|
||||
field(DESC, "Cleaning State Sequence")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(ZRST, "NonCleaning")
|
||||
field(ONST, "Cleaning1")
|
||||
field(TWST, "Cleaning2")
|
||||
field(THST, "Cleaning3")
|
||||
field(FRST, "Cleaning4")
|
||||
field(FVST, "Cleaning5")
|
||||
field(VAL, "0")
|
||||
}
|
||||
|
||||
record(mbbi, "$(P)$(R)WSHOTINGSTATE") {
|
||||
field(DESC, "Plasma Shot State Sequence")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(SXVL, "6")
|
||||
field(SVVL, "7")
|
||||
field(EIVL, "8")
|
||||
field(NIVL, "9")
|
||||
field(TEVL, "10")
|
||||
field(ELVL, "11")
|
||||
field(TVVL, "12")
|
||||
field(TTVL, "13")
|
||||
field(ZRST, "NonShooting")
|
||||
field(ONST, "ShotWTrig")
|
||||
field(TWST, "Shooting2")
|
||||
field(THST, "Shooting3")
|
||||
field(FRST, "Shooting4")
|
||||
field(FVST, "Shooting5")
|
||||
field(SXST, "Shooting6")
|
||||
field(SVST, "Shooting7")
|
||||
field(EIST, "Shooting8")
|
||||
field(NIST, "Shooting9")
|
||||
field(TEST, "Shooting10")
|
||||
field(ELST, "Shooting11")
|
||||
field(TVST, "Shooting12")
|
||||
field(TTST, "ShotEnd")
|
||||
field(VAL, "0")
|
||||
field(DESC, "Plasma Shot State Sequence")
|
||||
field(ZRVL, "0")
|
||||
field(ONVL, "1")
|
||||
field(TWVL, "2")
|
||||
field(THVL, "3")
|
||||
field(FRVL, "4")
|
||||
field(FVVL, "5")
|
||||
field(SXVL, "6")
|
||||
field(SVVL, "7")
|
||||
field(EIVL, "8")
|
||||
field(NIVL, "9")
|
||||
field(TEVL, "10")
|
||||
field(ELVL, "11")
|
||||
field(TVVL, "12")
|
||||
field(TTVL, "13")
|
||||
field(ZRST, "NonShooting")
|
||||
field(ONST, "ShotWTrig")
|
||||
field(TWST, "Shooting2")
|
||||
field(THST, "Shooting3")
|
||||
field(FRST, "Shooting4")
|
||||
field(FVST, "Shooting5")
|
||||
field(SXST, "Shooting6")
|
||||
field(SVST, "Shooting7")
|
||||
field(EIST, "Shooting8")
|
||||
field(NIST, "Shooting9")
|
||||
field(TEST, "Shooting10")
|
||||
field(ELST, "Shooting11")
|
||||
field(TVST, "Shooting12")
|
||||
field(TTST, "ShotEnd")
|
||||
field(VAL, "0")
|
||||
}
|
||||
|
||||
record(mbbi, "$(P)$(R)STOPPINGSTATE") {
|
||||
|
||||
@@ -1,18 +1,18 @@
|
||||
Terminator=CR;
|
||||
Terminator = CR;
|
||||
inTerminator = CR;
|
||||
# CR and LF are control characters, respectively coded 0x0D (13 decimal) and 0x0A (10 decimal)
|
||||
# CR and LF are control characters, respectively coded 0x0D (13 decimal) and 0x0A (10 decimal)
|
||||
MaxInput = 30;
|
||||
MaxInput = 20;
|
||||
ExtraInput = Ignore;
|
||||
|
||||
# Values in millisecond
|
||||
LockTimeout = 1000;
|
||||
LockTimeout = 500;
|
||||
# Affects first out command in a protocol.
|
||||
# If other records currently use the device, how many milliseconds to wait for
|
||||
# exclusive access to the device before giving up?
|
||||
|
||||
#ReadTimeout = 1500;
|
||||
|
||||
ReplyTimeout = 400;
|
||||
ReplyTimeout = 300;
|
||||
|
||||
#PollPeriod = $ReplyTimeout;
|
||||
#Integer. Affects first in command in I/O Intr mode (see chapter Record Processing).
|
||||
|
||||
@@ -1,8 +1,9 @@
|
||||
ISTTOK:central:PULSE-NUMBER.VAL
|
||||
# P=ISTTOK:,R=central:
|
||||
$(P)$(R)PULSE-NUMBER.VAL
|
||||
ISTTOK:central:LogMessage.VAL
|
||||
|
||||
ISTTOK:central:LASTOPSTATE.VAL
|
||||
ISTTOK:central:OPREQ
|
||||
ISTTOK:central:OPREQ.VAL
|
||||
ISTTOK:central:PROCESS-MODE.VAL
|
||||
ISTTOK:central:CLEANINGMANMODE.VAL
|
||||
|
||||
@@ -12,7 +13,7 @@ ISTTOK:central:Shot-TorPSCurrent
|
||||
ISTTOK:central:UPS-Shutdown
|
||||
|
||||
#ALARM Limits
|
||||
ISTTOK:central:RPump1-Pressure.HIGH
|
||||
$(P)$(R)RPump1-Pressure.HIGH
|
||||
ISTTOK:central:RPump1-Pressure.HIHI
|
||||
#ISTTOK:central:RPump2-Pressure.HIGH
|
||||
#ISTTOK:central:RPump2-Pressure.HIHI
|
||||
|
||||
@@ -1,8 +1,8 @@
|
||||
# autosave R5.3 Automatically generated - DO NOT MODIFY - 211214-141949
|
||||
# autosave R5.3 Automatically generated - DO NOT MODIFY - 211215-002448
|
||||
ISTTOK:central:PULSE-NUMBER.VAL 0
|
||||
ISTTOK:central:LogMessage.VAL
|
||||
ISTTOK:central:LASTOPSTATE.VAL 5
|
||||
ISTTOK:central:OPREQ 0
|
||||
ISTTOK:central:LASTOPSTATE.VAL 2
|
||||
ISTTOK:central:OPREQ.VAL 1
|
||||
ISTTOK:central:PROCESS-MODE.VAL 0
|
||||
ISTTOK:central:CLEANINGMANMODE.VAL 0
|
||||
ISTTOK:central:Emergency-UserButton.VAL 0
|
||||
|
||||
@@ -46,10 +46,10 @@ dbLoadRecords("db/sendmail.db", "P=ISTTOK:,PORT=L0,R=central:,L=0,A=0")
|
||||
|
||||
# Uncomment to Debug STREAMDEVICE serial activity
|
||||
# 2021/12/14 13:11:50.019969 RS0 ISTTOK:central:P002:M: No reply within 200 ms to "0020074002=?107<0d>
|
||||
#var streamError 1
|
||||
var streamError 1
|
||||
#with this no errors on pfeiffer bus
|
||||
var streamDebug 1
|
||||
streamSetLogfile("logfile.txt")
|
||||
#var streamDebug 1
|
||||
#streamSetLogfile("logfile.txt")
|
||||
|
||||
## Run this to trace the stages of iocInit
|
||||
#traceIocInit
|
||||
@@ -70,11 +70,11 @@ asSetFilename("${TOP}/iocBoot/${IOC}/access_security.acf")
|
||||
|
||||
iocInit
|
||||
|
||||
#asInit
|
||||
asInit
|
||||
|
||||
# Create request file and start periodic 'save’
|
||||
# makeAutosaveFileFromDbInfo("$(SAVE_DIR)/$(IOC).req", "autosaveFields")
|
||||
create_monitor_set("$(IOC).req", 30)
|
||||
create_monitor_set("$(IOC).req", 30, "P=ISTTOK:,R=central:")
|
||||
|
||||
## Start any sequence programs , use safe mode
|
||||
seq IsttokSeqExec "unit=ISTTOK"
|
||||
|
||||
Reference in New Issue