# This records is the dspPIC uptime in seconds from last reset #
###################################################################
record(longin, "$(P)$(R)Uptime")
{
field(DESC, "Reads dsPIC Uptime")
field(DTYP, "stream")
field(INP, "@dspic.proto getUP $(PORT)")
field(SCAN, "I/O Intr")
field(FLNK,"$(P)$(R)Diff_Uptime") #Link to update Diff_Uptime
field(ADEL,100)
field(MDEL,0)
}
record(calc, "$(P)$(R)Diff_Uptime") {
field(DESC, "Uptime diff. between I/O Intr scans")
field(CALC,"B-A")
field(SCAN,"Passive")
field(INPA,"$(P)$(R)Last_Uptime.VAL NPP")
field(INPB,"$(P)$(R)Uptime")
field(FLNK,"$(P)$(R)Last_Uptime")
field(HIHI,"100.0")
field(HIGH,"2.0")
field(LOW, "0.0")
field(LOLO,"-10.0")
}
record(calc, "$(P)$(R)Last_Uptime") {
field(DESC, "Last Uptime for diff. calc")
field(CALC,"A")
field(SCAN,"Passive")
field(INPA,"$(P)$(R)Uptime")
}
###################################################################
# These records read Temperatures #
###################################################################
record(ai, "$(P)$(R)VVessel-Temperature")
{
field(DESC, "Reads TE01 Temperature")
field(DTYP, "stream")
field(INP, "@dspic.proto getTE01 $(PORT) $(A)")
field(SCAN, "I/O Intr")
field(EGU, "C")
field(PREC, "4")
field(LINR, "LINEAR")
# field(ESLO, "0.00001163358")
# See https://paulscherrerinstitute.github.io/StreamDevice/ai.html
# field(EGUL, "-1.02376")
# x 30
field(ESLO, "0.000349007")
#field(EGUL, "-30.71")
field(EOFF, "-30.71")
field(HOPR, "140.0")
field(LOPR, "0.0")
field(HIHI,"130.0")
field(HIGH,"120.0")
field(LOW, "0.0")
field(LOLO,"-10.0")
field(HHSV,"MAJOR")
field(HSV, "MINOR")
# field(LSV, "MINOR")
# field(LLSV,"MAJOR")
field(ADEL, "1.0") # Archive Deadband
}
# Precision
# Engineering Units
# field(EGU, "Raw")
# Convertion
# val = val * ESLO + EGUL
# field(ESLO, "0.000011633582866550557")
# field(DESC,"Thermocouple 0")
# field(HIHI,"90.0")
# field(HIGH,"50.0")
# field(LOW, "20.0")
# field(LOLO,"0.0")
# field(HHSV,"MAJOR")
# field(HSV, "MINOR")
# field(LSV, "MINOR")
# field(LLSV,"MAJOR")
# field(MDEL, "0.0") # Monitor Deadband
record(ai, "$(P)$(R)Temperature_1")
{
field(DESC, "Reads TE02 Temperature")
field(DTYP, "stream")
field(INP, "@dspic.proto getTE02 $(PORT) $(A)")
field(SCAN, "I/O Intr")
field(EGU, "C")
field(PREC, "4")
field(LINR, "LINEAR")
# field(CALC,"A*0.000011633582866550557-1.02376")
field(ESLO, "0.00001163358")
field(EGUL, "-1.02376")
}
record(ai, "$(P)$(R)Temperature_2")
{
field(DESC, "Reads TE03 Temperature")
field(DTYP, "stream")
field(INP, "@dspic.proto getTE03 $(PORT)")
field(SCAN, "I/O Intr")
field(EGU, "C")
field(PREC, "4")
field(LINR, "LINEAR")
field(ESLO, "0.00001163358")
field(EGUL, "-1.02376")
}
record(ai, "$(P)$(R)Temperature_3") {
field(DESC, "Reads TE04 Temperature")
field(DTYP, "stream")
field(INP, "@dspic.proto getTE04 $(PORT)")
field(SCAN, "I/O Intr")
field(EGU, "C")
field(PREC, "4")
field(LINR, "LINEAR")
field(ESLO, "0.00001163358")
field(EGUL, "-1.02376")
}
record(ai, "$(P)$(R)Capbank_Voltage") {
field(DESC, "Reads PRD01, Capitor bank Voltage PWM")
field(DTYP, "stream")
field(INP, "@dspic.proto getPRD01 $(PORT)")
field(SCAN, "I/O Intr")
field(LINR, "LINEAR")
# # val = val * ESLO + EGUL
field(ESLO, "1.0")
field(EGUL, "0.0")
# Precision
field(PREC, "1")
# Units
field(EGU, "V")
# # Alarms
}
record(stringin, $(P)$(R)idn) {
field(DESC, "Debug info blabla")
field(DTYP, "stream")
field(INP, "@dspic.proto getStr $(PORT) $(A)")
field(SCAN, "I/O Intr")
}
record(stringin, "$(P)$(R)CurrentTime") {
field(DESC, "Current Date and Time of the IOC")
field(SCAN, "1 second")
field(DTYP, "Soft Timestamp")
field(PINI, "YES")
field(INP, "@%d/%m/%Y %H:%M:%S")
}