################################################################### # This records is the dspPIC uptime in seconds from last reset # ################################################################### record(longin, "$(P)$(R)Uptime") { field(PINI, "1") field(DTYP, "asynInt32") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_UPTIME") field(SCAN, "I/O Intr") field(FLNK,"$(P)$(R)Diff_Uptime") #Link to update Diff_Uptime } record(calc, "$(P)$(R)Diff_Uptime") { field(DESC, "Uptime diff. between I/O Intr scans") field(CALC,"B-A") field(SCAN,"Passive") field(INPA,"$(P)$(R)Last_Uptime.VAL NPP") field(INPB,"$(P)$(R)Uptime") field(FLNK,"$(P)$(R)Last_Uptime") field(HIHI,"100.0") field(HIGH,"2.0") field(LOW, "0.0") field(LOLO,"-10.0") } record(calc, "$(P)$(R)Last_Uptime") { field(DESC, "Last Uptime for diff. calc") field(CALC,"A") field(SCAN,"Passive") field(INPA,"$(P)$(R)Uptime") # field(INPB,"$(P)$(R)Uptime PP") } ################################################################### # These records control Valve Open/Close # ################################################################### record(bo, "$(P)$(R)Valve_1") { field(PINI, "0") field(DTYP, "asynInt32") field(OUT, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_CHANGE_1") field(ZNAM, "Close") # Off field(ONAM, "Open") } record(bi, "$(P)$(R)Valve_1_RBV") { field(PINI, "1") field(DTYP, "asynInt32") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_STATE_1") field(ZNAM, "Closed") field(ZSV, "NO_ALARM") field(ONAM, "Opened") field(OSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "$(P)$(R)Valve_2") { field(PINI, "0") field(DTYP, "asynInt32") field(OUT, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_CHANGE_2") field(ZNAM, "Close") # Off field(ONAM, "Open") } record(bi, "$(P)$(R)Valve_2_RBV") { field(PINI, "1") field(DTYP, "asynInt32") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_STATE_2") field(ZNAM, "Closed") field(ZSV, "NO_ALARM") field(ONAM, "Opened") field(OSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "$(P)$(R)Valve_3") { field(PINI, "0") field(DTYP, "asynInt32") field(OUT, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_CHANGE_3") field(ZNAM, "Close") # Off field(ONAM, "Open") } record(bi, "$(P)$(R)Valve_3_RBV") { field(PINI, "1") field(DTYP, "asynInt32") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_STATE_3") field(ZNAM, "Closed") field(ZSV, "NO_ALARM") field(ONAM, "Opened") field(OSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "$(P)$(R)Valve_4") { field(PINI, "0") field(DTYP, "asynInt32") field(OUT, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_CHANGE_4") field(ZNAM, "Close") # Off field(ONAM, "Open") } record(bi, "$(P)$(R)Valve_4_RBV") { field(PINI, "1") field(DTYP, "asynInt32") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_STATE_4") field(ZNAM, "Closed") field(ZSV, "NO_ALARM") field(ONAM, "Opened") field(OSV, "MINOR") field(SCAN, "I/O Intr") } ################################################################### # These records read Temperatures # ################################################################### record(ai, "$(P)$(R)Temperature_0") { field(PINI, "1") field(DTYP, "asynFloat64") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_0_VAL") # field(PREC, "5") field(DESC,"IN-SUP") field(SCAN, "I/O Intr") field(HIHI,"90.0") field(HIGH,"50.0") field(LOW, "20.0") field(LOLO,"0.0") field(HHSV,"MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(LLSV,"MAJOR") field(ADEL, "1.0") # Archive Deadband field(MDEL, "0.0") # Monitor Deadband # Engineering Units field(EGU, "Celcius") } record(ai, "$(P)$(R)Temperature_1") { field(PINI, "1") field(DTYP, "asynFloat64") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_1_VAL") # field(PREC, "5") field(DESC,"DEP. INFERIOR") field(SCAN, "I/O Intr") field(HIHI,"90.0") field(HIGH,"50.0") field(LOW, "20.0") field(LOLO,"0.0") field(HHSV,"MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(LLSV,"MAJOR") field(ADEL, "1.0") # Archive Deadband field(MDEL, "0.0") # Monitor Deadband # Engineering Units field(EGU, "Celcius") } record(ai, "$(P)$(R)Temperature_2") { field(PINI, "1") field(DTYP, "asynFloat64") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_2_VAL") # field(PREC, "5") field(DESC,"BYPASS") field(SCAN, "I/O Intr") field(HIHI,"90.0") field(HIGH,"50.0") field(LOW, "20.0") field(LOLO,"0.0") field(HHSV,"MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(LLSV,"MAJOR") field(ADEL, "1.0") # Archive Deadband field(MDEL, "0.0") # Monitor Deadband # Engineering Units field(EGU, "Celcius") } record(ai, "$(P)$(R)Temperature_3") { field(PINI, "1") field(DTYP, "asynFloat64") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_3_VAL") # field(PREC, "5") field(DESC,"TROCO INFERIOR") field(SCAN, "I/O Intr") field(HIHI,"90.0") field(HIGH,"50.0") field(LOW, "20.0") field(LOLO,"0.0") field(HHSV,"MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(LLSV,"MAJOR") field(ADEL, "1.0") # Archive Deadband field(MDEL, "0.0") # Monitor Deadband # Engineering Units field(EGU, "Celcius") } record(ai, "$(P)$(R)Temperature_4") { field(PINI, "1") field(DTYP, "asynFloat64") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_4_VAL") # field(PREC, "5") field(DESC,"DEP. SUPERIOR") field(SCAN, "I/O Intr") field(HIHI,"90.0") field(HIGH,"50.0") field(LOW, "20.0") field(LOLO,"0.0") field(HHSV,"MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(LLSV,"MAJOR") field(ADEL, "1.0") # Archive Deadband field(MDEL, "0.0") # Monitor Deadband # Engineering Units field(EGU, "Celcius") } record(ai, "$(P)$(R)Temperature_5") { field(PINI, "1") field(DTYP, "asynFloat64") field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_5_VAL") # field(PREC, "5") field(DESC,"COLECTOR") field(SCAN, "I/O Intr") field(HIHI,"90.0") field(HIGH,"50.0") field(LOW, "20.0") field(LOLO,"0.0") field(HHSV,"MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(LLSV,"MAJOR") field(ADEL, "1.0") # Archive Deadband field(MDEL, "0.0") # Monitor Deadband # Engineering Units field(EGU, "Celcius") } ################################################################### # Test records # ################################################################### record(ai, "$(P)$(R)test_ai") { field(DESC,"test record say: Hello World") }