Paulo modifications
This commit is contained in:
@@ -1,175 +1,8 @@
|
||||
##########
|
||||
# Relays #
|
||||
##########
|
||||
record( bo, "$(P)$(R)RotatoryPump" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B7 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
record( bo, "$(P)$(R)RotatoryValve" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B6 PP" )
|
||||
field( ZNAM, "Open" )
|
||||
field( ONAM, "Closed" )
|
||||
}
|
||||
|
||||
##############################
|
||||
# BUZZER ON/OFF #
|
||||
##############################
|
||||
record(bo, "$(P)$(R)BuzzerOnOff" ) {
|
||||
field( ZNAM, "Off" )
|
||||
field( ONAM, "Pulse" )
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)BuzzerOnOffInv" )
|
||||
}
|
||||
record(calcout, "$(P)$(R)BuzzerOnOffInv" ) {
|
||||
field( INPA, "$(P)$(R)BuzzerOnOff NPP MS" )
|
||||
#field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B5 PP MS" )
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B5 PP MS" )
|
||||
field( OOPT, "On Change" )
|
||||
field( CALC, "A?0:1" )
|
||||
}
|
||||
|
||||
##############################
|
||||
# LIGHTS ON/OFF #
|
||||
##############################
|
||||
record(bo, "$(P)$(R)LightsOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B4 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
record(bi , "$(P)$(R)LightsOnOff-G" ) {
|
||||
field( INP, "$(P)$(R)PCF8574:60:REGISTER:READ.B4 NPP NMS")
|
||||
field( SCAN, "1 second")
|
||||
field( ZNAM, "ON" )
|
||||
field( ONAM, "OFF" )
|
||||
}
|
||||
|
||||
##################################
|
||||
# GIS VALVES ON/OFF #
|
||||
##################################
|
||||
record(bo, "$(P)$(R)GISValvesOnOff" ) {
|
||||
#field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B3 PP" )
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B4 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
################################
|
||||
# FILAMENT ON/OFF #
|
||||
################################
|
||||
record(bo, "$(P)$(R)FilamentOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B2 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
##########################################
|
||||
# CAP BANK CONNECTOR ON/OFF #
|
||||
##########################################
|
||||
record(bo, "$(P)$(R)CapBankConOnOff" ) {
|
||||
#field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B1 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
###############################
|
||||
### PRIMARY CLEANING ON/OFF ###
|
||||
###############################
|
||||
record(bo, "$(P)$(R)PrimaryCleaningOnOff"){
|
||||
field( DESC, "Primary Cleaning OnOff")
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B1 PP" )
|
||||
field( ZNAM, "On")
|
||||
field( ONAM, "Off")
|
||||
}
|
||||
|
||||
#######################################
|
||||
# CAP BANK CHARGE ON/OFF #
|
||||
#######################################
|
||||
record(bo, "$(P)$(R)CapBankChargeOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B0 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
####################################
|
||||
# TIMING TRIGGER ON/OFF #
|
||||
####################################
|
||||
record(bi , "$(P)$(R)TimingTriggerSignal" ) {
|
||||
field( INP, "$(P)$(R)PCF8574:57:REGISTER:READ.B7")
|
||||
field( SCAN, "1 second" )
|
||||
field( ZNAM, "OFF" )
|
||||
field( ONAM, "ON" )
|
||||
}
|
||||
|
||||
##########################################
|
||||
# CAP BANK DISCHARGE ON/OFF #
|
||||
##########################################
|
||||
record(bo, "$(P)$(R)CapBankDischargeOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B6 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
##################################
|
||||
# PPS BAKING ON/OFF #
|
||||
##################################
|
||||
record(bo, "$(P)$(R)BakingPPSOnOff" ) {
|
||||
#field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B5 PP" )
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B5 PP MS" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
###################################
|
||||
# TRANSFORMER ON/OFF #
|
||||
###################################
|
||||
#record(bo, "$(P)$(R)TransformerOnOff" ) {
|
||||
# field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B4 PP" )
|
||||
# field( ZNAM, "On" )
|
||||
# field( ONAM, "Off" )
|
||||
#}
|
||||
|
||||
######################################
|
||||
# TRANSFORMER500 ON/OFF #
|
||||
######################################
|
||||
record(bo, "$(P)$(R)Trans500OnOff" ) {
|
||||
#field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B4 PP" )
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B3 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
######################################
|
||||
# TRANS TO POWER ON/OFF #
|
||||
######################################
|
||||
record(bo, "$(P)$(R)TransToPowerOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B3 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
#############################
|
||||
# ROTARY PUMP2 #
|
||||
#############################
|
||||
record( bo, "$(P)$(R)RotatoryPump2" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B2 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
record( bo, "$(P)$(R)RotatoryValve2" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B1 PP" )
|
||||
field( ZNAM, "Open" )
|
||||
field( ONAM, "Closed" )
|
||||
}
|
||||
|
||||
##############################
|
||||
# EMERGENCY MODE #
|
||||
##############################
|
||||
record( bo, "$(P)$(R)EmergencyModeOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B0 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off")
|
||||
}
|
||||
###############
|
||||
###############
|
||||
# REGISTER 56 #
|
||||
###############
|
||||
###############
|
||||
|
||||
#####################################
|
||||
### 24V commands - Optocoupler Out###
|
||||
@@ -180,42 +13,49 @@ record(bo, "$(P)$(R)TMPControllerOn" ) {
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)TMPControllerOnInv" )
|
||||
}
|
||||
|
||||
record(calcout, "$(P)$(R)TMPControllerOnInv" ) {
|
||||
field( INPA, "$(P)$(R)TMPControllerOn NPP MS" )
|
||||
field( OUT, "$(P)$(R)PCF8574:56:REGISTER.B0 PP MS" )
|
||||
field( OOPT, "On Change" )
|
||||
field( CALC, "A?0:1" )
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)TMPControllerOff" ) {
|
||||
field( ZNAM, "Off" )
|
||||
field( ONAM, "Pulse" )
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)TMPControllerOffInv" )
|
||||
}
|
||||
|
||||
record(calcout, "$(P)$(R)TMPControllerOffInv") {
|
||||
field( INPA, "$(P)$(R)TMPControllerOff NPP MS" )
|
||||
field( OUT, "$(P)$(R)PCF8574:56:REGISTER.B1 PP MS")
|
||||
field( OOPT, "On Change" )
|
||||
field( CALC, "A?0:1" )
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)TMPMotorOn" ) {
|
||||
field( ZNAM, "Off")
|
||||
field( ONAM, "Pulse")
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)TMPMotorOnInv")
|
||||
}
|
||||
|
||||
record(calcout, "$(P)$(R)TMPMotorOnInv" ) {
|
||||
field( INPA, "$(P)$(R)TMPMotorOn NPP MS")
|
||||
field( OUT, "$(P)$(R)PCF8574:56:REGISTER.B2 PP MS")
|
||||
field( OOPT, "On Change")
|
||||
field( CALC, "A?0:1" )
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)TMPMotorOff") {
|
||||
field( ZNAM, "Off")
|
||||
field( ONAM, "Pulse")
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)TMPMotorOffInv")
|
||||
}
|
||||
|
||||
record(calcout, "$(P)$(R)TMPMotorOffInv") {
|
||||
field( INPA, "$(P)$(R)TMPMotorOff NPP MS")
|
||||
field( OUT, "$(P)$(R)PCF8574:56:REGISTER.B3 PP MS")
|
||||
@@ -233,124 +73,245 @@ record(bi , "$(P)$(R)Turbo_PW_Ind" ) {
|
||||
field( ONAM, "OFF" )
|
||||
field(FLNK, "$(P)$(R)Turbo_Emergency")
|
||||
}
|
||||
|
||||
record(bi , "$(P)$(R)Turbo_Emergency") {
|
||||
field( INP, "$(P)$(R)PCF8574:56:REGISTER:READ.B5 NPP NMS")
|
||||
field( ZNAM, "ON" )
|
||||
field( ONAM, "OFF" )
|
||||
field(FLNK, "$(P)$(R)Turbo_Acceleration")
|
||||
}
|
||||
|
||||
record(bi , "$(P)$(R)Turbo_Acceleration") {
|
||||
field( INP, "$(P)$(R)PCF8574:56:REGISTER:READ.B6 NPP NMS")
|
||||
field( ZNAM, "ON" )
|
||||
field( ONAM, "OFF" )
|
||||
field(FLNK, "$(P)$(R)Turbo_NormalOperation")
|
||||
}
|
||||
|
||||
record(bi , "$(P)$(R)Turbo_NormalOperation" ) {
|
||||
field( INP, "$(P)$(R)PCF8574:56:REGISTER:READ.B7 NPP NMS")
|
||||
field( ZNAM, "ON" )
|
||||
field( ONAM, "OFF" )
|
||||
}
|
||||
|
||||
#####################################
|
||||
### 24V commands - Optocoupler Out###
|
||||
#####################################
|
||||
record(bo, "$(P)$(R)TMP2ControllerOn" ) {
|
||||
field( ZNAM, "Off" )
|
||||
field( ONAM, "Pulse" )
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)TMP2ControllerOnInv" )
|
||||
}
|
||||
record(calcout, "$(P)$(R)TMP2ControllerOnInv" ) {
|
||||
field( INPA, "$(P)$(R)TMP2ControllerOn NPP MS" )
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B0 PP MS" )
|
||||
field( OOPT, "On Change" )
|
||||
field( CALC, "A?0:1" )
|
||||
}
|
||||
record(bo, "$(P)$(R)TMP2ControllerOff" ) {
|
||||
field( ZNAM, "Off" )
|
||||
field( ONAM, "Pulse" )
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)TMP2ControllerOffInv" )
|
||||
}
|
||||
record(calcout, "$(P)$(R)TMP2ControllerOffInv") {
|
||||
field( INPA, "$(P)$(R)TMP2ControllerOff NPP MS" )
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B1 PP MS")
|
||||
field( OOPT, "On Change" )
|
||||
field( CALC, "A?0:1" )
|
||||
}
|
||||
record(bo, "$(P)$(R)TMP2MotorOn" ) {
|
||||
field( ZNAM, "Off")
|
||||
field( ONAM, "Pulse")
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)TMP2MotorOnInv")
|
||||
}
|
||||
record(calcout, "$(P)$(R)TMP2MotorOnInv" ) {
|
||||
field( INPA, "$(P)$(R)TMP2MotorOn NPP MS")
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B2 PP MS")
|
||||
field( OOPT, "On Change")
|
||||
field( CALC, "A?0:1" )
|
||||
}
|
||||
record(bo, "$(P)$(R)TMP2MotorOff") {
|
||||
field( ZNAM, "Off")
|
||||
field( ONAM, "Pulse")
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)TMP2MotorOffInv")
|
||||
}
|
||||
record(calcout, "$(P)$(R)TMP2MotorOffInv") {
|
||||
field( INPA, "$(P)$(R)TMP2MotorOff NPP MS")
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B3 PP MS")
|
||||
field( OOPT, "On Change")
|
||||
field( CALC, "A?0:1")
|
||||
}
|
||||
###############
|
||||
###############
|
||||
# REGISTER 57 #
|
||||
###############
|
||||
###############
|
||||
|
||||
#########################################
|
||||
# TOR-FIELD TRIGGER ON/OFF BO #
|
||||
#########################################
|
||||
record(bi, "$(P)$(R)TorFieldTriggerOnOff" ) {
|
||||
#field( INP, "$(P)$(R)PCF8574:61:REGISTER:READ.B3 NPP NMS" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
field( VAL, 1)
|
||||
}
|
||||
|
||||
#############################
|
||||
### TMP2 Controller inputs###
|
||||
#############################
|
||||
record(bi , "$(P)$(R)Turbo2_PW_Ind" ) {
|
||||
field( INP, "$(P)$(R)PCF8574:61:REGISTER:READ.B4 PP NMS")
|
||||
field( SCAN, "1 second")
|
||||
field( ZNAM, "ON" )
|
||||
field( ONAM, "OFF" )
|
||||
field(FLNK, "$(P)$(R)Turbo2_Emergency")
|
||||
}
|
||||
##############################
|
||||
### TMP2 Controller Inputs ###
|
||||
##############################
|
||||
record(bi , "$(P)$(R)Turbo2_Emergency") {
|
||||
field( INP, "$(P)$(R)PCF8574:61:REGISTER:READ.B5 NPP NMS")
|
||||
field( INP, "$(P)$(R)PCF8574:57:REGISTER:READ.B0 NPP NMS")
|
||||
field( ZNAM, "ON" )
|
||||
field( ONAM, "OFF" )
|
||||
field(FLNK, "$(P)$(R)Turbo2_Acceleration")
|
||||
}
|
||||
|
||||
record(bi , "$(P)$(R)Turbo2_Acceleration") {
|
||||
field( INP, "$(P)$(R)PCF8574:61:REGISTER:READ.B6 NPP NMS")
|
||||
field( ZNAM, "ON" )
|
||||
field( ONAM, "OFF" )
|
||||
field(FLNK, "$(P)$(R)Turbo2_NormalOperation")
|
||||
}
|
||||
record(bi , "$(P)$(R)Turbo2_NormalOperation" ) {
|
||||
field( INP, "$(P)$(R)PCF8574:61:REGISTER:READ.B7 NPP NMS")
|
||||
field( INP, "$(P)$(R)PCF8574:57:REGISTER:READ.B1 NPP NMS")
|
||||
field( ZNAM, "ON" )
|
||||
field( ONAM, "OFF" )
|
||||
}
|
||||
|
||||
#######################
|
||||
###TMP1 Manual Valve###
|
||||
#######################
|
||||
record(bo, "$(P)$(R)TMPManualValve"){
|
||||
info(autosaveFields, "VAL")
|
||||
field( DESC, "State of manual valve")
|
||||
field( ZNAM, "Closed")
|
||||
field( ONAM, "Open")
|
||||
###############################
|
||||
### TMP2 Controller Outputs ###
|
||||
###############################
|
||||
record(bo, "$(P)$(R)TMP2MotorOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B2 PP MS")
|
||||
field( ZNAM, "ON")
|
||||
field( ONAM, "OFF")
|
||||
}
|
||||
|
||||
##############################
|
||||
# BUZZER ON/OFF #
|
||||
##############################
|
||||
record(bo, "$(P)$(R)BuzzerOnOff" ) {
|
||||
field( ZNAM, "Off" )
|
||||
field( ONAM, "Pulse" )
|
||||
field( HIGH, "2.5")
|
||||
field( FLNK, "$(P)$(R)BuzzerOnOffInv" )
|
||||
}
|
||||
record(calcout, "$(P)$(R)BuzzerOnOffInv" ) {
|
||||
field( INPA, "$(P)$(R)BuzzerOnOff NPP MS" )
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B3 PP MS" )
|
||||
field( OOPT, "On Change" )
|
||||
field( CALC, "A?0:1" )
|
||||
}
|
||||
|
||||
##############################
|
||||
# EMERGENCY MODE #
|
||||
##############################
|
||||
record( bo, "$(P)$(R)EmergencyOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:57:REGISTER.B4 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off")
|
||||
}
|
||||
|
||||
############
|
||||
# NOT USED #
|
||||
############
|
||||
#$(P)$(R)PCF8574:57:REGISTER:READ.B5
|
||||
#$(P)$(R)PCF8574:57:REGISTER:READ.B6
|
||||
|
||||
####################################
|
||||
# TIMING TRIGGER ON/OFF #
|
||||
####################################
|
||||
record(bi , "$(P)$(R)TimingTriggerSignal" ) {
|
||||
field( INP, "$(P)$(R)PCF8574:57:REGISTER:READ.B7")
|
||||
field( SCAN, "1 second" )
|
||||
field( ZNAM, "OFF" )
|
||||
field( ONAM, "ON" )
|
||||
}
|
||||
|
||||
###############
|
||||
###############
|
||||
# REGISTER 60 #
|
||||
###############
|
||||
###############
|
||||
|
||||
#############################
|
||||
# ROTARY1 PUMP #
|
||||
#############################
|
||||
record( bo, "$(P)$(R)RotatoryPump" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B0 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
#############################
|
||||
# ROTARY1 VALVE #
|
||||
#############################
|
||||
record( bo, "$(P)$(R)RotatoryValve" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B1 PP" )
|
||||
field( ZNAM, "Open" )
|
||||
field( ONAM, "Closed" )
|
||||
}
|
||||
|
||||
#############################
|
||||
# ROTARY2 PUMP #
|
||||
#############################
|
||||
record( bo, "$(P)$(R)RotatoryPump2" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B2 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
#############################
|
||||
# ROTARY2 VALVE #
|
||||
#############################
|
||||
record( bo, "$(P)$(R)RotatoryValve2" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B3 PP" )
|
||||
field( ZNAM, "Open" )
|
||||
field( ONAM, "Closed" )
|
||||
}
|
||||
|
||||
################################
|
||||
# FILAMENT ON/OFF #
|
||||
################################
|
||||
record(bo, "$(P)$(R)FilamentOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B4 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
##############################
|
||||
# LIGHTS ON/OFF #
|
||||
##############################
|
||||
record(bo, "$(P)$(R)LightsOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B5 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
############
|
||||
# NOT USED #
|
||||
############
|
||||
#$(P)$(R)PCF8574:60:REGISTER:READ.B6
|
||||
|
||||
##############################
|
||||
# TOR CLEAN CONTACTOR ON/OFF #
|
||||
##############################
|
||||
record(bo, "$(P)$(R)ToroidalCleanContactorOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:60:REGISTER.B7 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
###############
|
||||
###############
|
||||
# REGISTER 61 #
|
||||
###############
|
||||
###############
|
||||
|
||||
############################
|
||||
# TOR CLEAN BREAKER ON/OFF #
|
||||
############################
|
||||
record(bo, "$(P)$(R)ToroidalCleanBreakerOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B0 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)ToroidalShotEnableOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B1 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)ToroidalShotTriggerOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B2 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
#######################################
|
||||
# CAP BANK CHARGE ON/OFF #
|
||||
#######################################
|
||||
record(bo, "$(P)$(R)CapBankChargeOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B3 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
########################################
|
||||
# PRIMARY CLEAN CONTACTOR ON/OFF #
|
||||
########################################
|
||||
record(bo, "$(P)$(R)PrimaryCleanContactorOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B4 PP MS" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
####################################
|
||||
### PRIMARY CLEAN BREAKER ON/OFF ###
|
||||
####################################
|
||||
record(bo, "$(P)$(R)PrimaryCleanBreakerOnOff"){
|
||||
field( DESC, "Primary Cleaning OnOff")
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B5 PP" )
|
||||
field( ZNAM, "On")
|
||||
field( ONAM, "Off")
|
||||
}
|
||||
|
||||
##################################
|
||||
# GIS VALVES ON/OFF #
|
||||
##################################
|
||||
record(bo, "$(P)$(R)GISValvesOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B6 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
##########################################
|
||||
# CAP BANK DISCHARGE ON/OFF #
|
||||
##########################################
|
||||
record(bo, "$(P)$(R)CapBankDischargeOnOff" ) {
|
||||
field( OUT, "$(P)$(R)PCF8574:61:REGISTER.B7 PP" )
|
||||
field( ZNAM, "On" )
|
||||
field( ONAM, "Off" )
|
||||
}
|
||||
|
||||
#########################
|
||||
###Pressure Conditions###
|
||||
@@ -376,11 +337,12 @@ record(ai,"$(P)$(R)Bypass_Condition"){
|
||||
field(VAL,"0")
|
||||
}
|
||||
|
||||
#####################
|
||||
###Dummy Variables###
|
||||
#####################
|
||||
record(ao,"$(P)$(R)Pressure_TMP_admission"){
|
||||
field(VAL,"1.0e5")
|
||||
field(PREC,"3")
|
||||
field(EGU,"mBar")
|
||||
#######################
|
||||
###TMP1 Manual Valve###
|
||||
#######################
|
||||
record(bo, "$(P)$(R)TMPManualValve"){
|
||||
info(autosaveFields, "VAL")
|
||||
field( DESC, "State of manual valve")
|
||||
field( ZNAM, "Closed")
|
||||
field( ONAM, "Open")
|
||||
}
|
||||
|
||||
Reference in New Issue
Block a user