Moved pfeffer sensors to cenrtal IOC

This commit is contained in:
Bernardo Carvalho
2021-12-14 14:19:56 +00:00
parent f5aa69298b
commit ecae668588
7 changed files with 123 additions and 63 deletions

View File

@@ -1,23 +1,43 @@
Terminator=CR;
MaxInput = 20;
# CR and LF are control characters, respectively coded 0x0D (13 decimal) and 0x0A (10 decimal)
# CR and LF are control characters, respectively coded 0x0D (13 decimal) and 0x0A (10 decimal)
MaxInput = 30;
ExtraInput = Ignore;
# Values in millisecond
LockTimeout = 1000;
# Affects first out command in a protocol.
# If other records currently use the device, how many milliseconds to wait for
# exclusive access to the device before giving up?
#ReadTimeout = 1500;
ReplyTimeout = 400;
#PollPeriod = $ReplyTimeout;
#Integer. Affects first in command in I/O Intr mode (see chapter Record Processing).
PollPeriod = 200;
# in millisecond
#ReadTimeout = 2000;
ReplyTimeout = 250;
# Using redirection to read 2 records, mantissa and exponent
# TMPump1-PressureAdmission
getPressure001 {
out "0010074002=?106";
in "0011074006%4u%(\$1)2u%+<sum8>";
}
#RPump1-Pressure
getPressure002 {
out "0020074002=?107";
in "0021074006%4u%(\$1)2u%+<sum8>";
}
#VVessel-Pressure
getPressure003 {
out "0030074002=?108";
in "0031074006%4u%(\$1)2u%+<sum8>";
}
getPressure004 {
out "0040074002=?109";
in "0041074006%4u%(\$1)2u%+<sum8>";