Imported IOC APP from SVN
This commit is contained in:
242
epics/iocs/dsPICtemperature/ISTTOKApp/Db/serialPicAPDriver.db
Normal file
242
epics/iocs/dsPICtemperature/ISTTOKApp/Db/serialPicAPDriver.db
Normal file
@@ -0,0 +1,242 @@
|
||||
###################################################################
|
||||
# This records is the dspPIC uptime in seconds from last reset #
|
||||
###################################################################
|
||||
|
||||
record(longin, "$(P)$(R)Uptime")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynInt32")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_UPTIME")
|
||||
field(SCAN, "I/O Intr")
|
||||
}
|
||||
|
||||
###################################################################
|
||||
# These records control Valve Open/Close #
|
||||
###################################################################
|
||||
record(bo, "$(P)$(R)Valve_1")
|
||||
{
|
||||
field(PINI, "0")
|
||||
field(DTYP, "asynInt32")
|
||||
field(OUT, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_1_STATE")
|
||||
field(ZNAM, "Close") # Off
|
||||
field(ONAM, "Open")
|
||||
}
|
||||
|
||||
record(bi, "$(P)$(R)Valve_1_RBV")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynInt32")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_1_STATE")
|
||||
field(ZNAM, "Closed")
|
||||
field(ZSV, "NO_ALARM")
|
||||
field(ONAM, "Openned")
|
||||
field(OSV, "MINOR")
|
||||
field(SCAN, "I/O Intr")
|
||||
}
|
||||
|
||||
record(bo, "$(P)$(R)Valve_2")
|
||||
{
|
||||
field(PINI, "0")
|
||||
field(DTYP, "asynInt32")
|
||||
field(OUT, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_2_STATE")
|
||||
field(ZNAM, "Close") # Off
|
||||
field(ONAM, "Open")
|
||||
}
|
||||
|
||||
record(bi, "$(P)$(R)Valve_2_RBV")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynInt32")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_2_STATE")
|
||||
field(ZNAM, "Closed")
|
||||
field(ZSV, "NO_ALARM")
|
||||
field(ONAM, "Openned")
|
||||
field(OSV, "MINOR")
|
||||
field(SCAN, "I/O Intr")
|
||||
}
|
||||
record(bo, "$(P)$(R)Valve_3")
|
||||
{
|
||||
field(PINI, "0")
|
||||
field(DTYP, "asynInt32")
|
||||
field(OUT, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_3_STATE")
|
||||
field(ZNAM, "Close") # Off
|
||||
field(ONAM, "Open")
|
||||
}
|
||||
|
||||
record(bi, "$(P)$(R)Valve_3_RBV")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynInt32")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_3_STATE")
|
||||
field(ZNAM, "Closed")
|
||||
field(ZSV, "NO_ALARM")
|
||||
field(ONAM, "Openned")
|
||||
field(OSV, "MINOR")
|
||||
field(SCAN, "I/O Intr")
|
||||
}
|
||||
record(bo, "$(P)$(R)Valve_4")
|
||||
{
|
||||
field(PINI, "0")
|
||||
field(DTYP, "asynInt32")
|
||||
field(OUT, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_4_STATE")
|
||||
field(ZNAM, "Close") # Off
|
||||
field(ONAM, "Open")
|
||||
}
|
||||
|
||||
record(bi, "$(P)$(R)Valve_4_RBV")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynInt32")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_VALVE_4_STATE")
|
||||
field(ZNAM, "Closed")
|
||||
field(ZSV, "NO_ALARM")
|
||||
field(ONAM, "Openned")
|
||||
field(OSV, "MINOR")
|
||||
field(SCAN, "I/O Intr")
|
||||
}
|
||||
|
||||
###################################################################
|
||||
# These records read Temperatures #
|
||||
###################################################################
|
||||
|
||||
record(ai, "$(P)$(R)Temperature_0")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynFloat64")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_0_VAL")
|
||||
# field(PREC, "5")
|
||||
field(DESC,"IN-SUP")
|
||||
field(SCAN, "I/O Intr")
|
||||
field(HIHI,"90.0")
|
||||
field(HIGH,"50.0")
|
||||
field(LOW, "20.0")
|
||||
field(LOLO,"0.0")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
field(LSV, "MINOR")
|
||||
field(LLSV,"MAJOR")
|
||||
field(ADEL, "1.0") # Archive Deadband
|
||||
field(MDEL, "0.0") # Monitor Deadband
|
||||
# Engineering Units
|
||||
field(EGU, "Celcius")
|
||||
}
|
||||
|
||||
record(ai, "$(P)$(R)Temperature_1")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynFloat64")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_1_VAL")
|
||||
# field(PREC, "5")
|
||||
field(DESC,"DEP. INFERIOR")
|
||||
field(SCAN, "I/O Intr")
|
||||
field(HIHI,"90.0")
|
||||
field(HIGH,"50.0")
|
||||
field(LOW, "20.0")
|
||||
field(LOLO,"0.0")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
field(LSV, "MINOR")
|
||||
field(LLSV,"MAJOR")
|
||||
field(ADEL, "1.0") # Archive Deadband
|
||||
field(MDEL, "0.0") # Monitor Deadband
|
||||
# Engineering Units
|
||||
field(EGU, "Celcius")
|
||||
}
|
||||
|
||||
record(ai, "$(P)$(R)Temperature_2")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynFloat64")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_2_VAL")
|
||||
# field(PREC, "5")
|
||||
field(DESC,"BYPASS")
|
||||
field(SCAN, "I/O Intr")
|
||||
field(HIHI,"90.0")
|
||||
field(HIGH,"50.0")
|
||||
field(LOW, "20.0")
|
||||
field(LOLO,"0.0")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
field(LSV, "MINOR")
|
||||
field(LLSV,"MAJOR")
|
||||
field(ADEL, "1.0") # Archive Deadband
|
||||
field(MDEL, "0.0") # Monitor Deadband
|
||||
# Engineering Units
|
||||
field(EGU, "Celcius")
|
||||
}
|
||||
|
||||
record(ai, "$(P)$(R)Temperature_3")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynFloat64")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_3_VAL")
|
||||
# field(PREC, "5")
|
||||
field(DESC,"TROCO INFERIOR")
|
||||
field(SCAN, "I/O Intr")
|
||||
field(HIHI,"90.0")
|
||||
field(HIGH,"50.0")
|
||||
field(LOW, "20.0")
|
||||
field(LOLO,"0.0")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
field(LSV, "MINOR")
|
||||
field(LLSV,"MAJOR")
|
||||
field(ADEL, "1.0") # Archive Deadband
|
||||
field(MDEL, "0.0") # Monitor Deadband
|
||||
# Engineering Units
|
||||
field(EGU, "Celcius")
|
||||
}
|
||||
|
||||
record(ai, "$(P)$(R)Temperature_4")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynFloat64")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_4_VAL")
|
||||
# field(PREC, "5")
|
||||
field(DESC,"DEP. SUPERIOR")
|
||||
field(SCAN, "I/O Intr")
|
||||
field(HIHI,"90.0")
|
||||
field(HIGH,"50.0")
|
||||
field(LOW, "20.0")
|
||||
field(LOLO,"0.0")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
field(LSV, "MINOR")
|
||||
field(LLSV,"MAJOR")
|
||||
field(ADEL, "1.0") # Archive Deadband
|
||||
field(MDEL, "0.0") # Monitor Deadband
|
||||
# Engineering Units
|
||||
field(EGU, "Celcius")
|
||||
}
|
||||
|
||||
record(ai, "$(P)$(R)Temperature_5")
|
||||
{
|
||||
field(PINI, "1")
|
||||
field(DTYP, "asynFloat64")
|
||||
field(INP, "@asyn($(PORT),$(ADDR),$(TIMEOUT))PIC_TEMP_5_VAL")
|
||||
# field(PREC, "5")
|
||||
field(DESC,"COLECTOR")
|
||||
field(SCAN, "I/O Intr")
|
||||
field(HIHI,"90.0")
|
||||
field(HIGH,"50.0")
|
||||
field(LOW, "20.0")
|
||||
field(LOLO,"0.0")
|
||||
field(HHSV,"MAJOR")
|
||||
field(HSV, "MINOR")
|
||||
field(LSV, "MINOR")
|
||||
field(LLSV,"MAJOR")
|
||||
field(ADEL, "1.0") # Archive Deadband
|
||||
field(MDEL, "0.0") # Monitor Deadband
|
||||
# Engineering Units
|
||||
field(EGU, "Celcius")
|
||||
}
|
||||
|
||||
###################################################################
|
||||
# Test records #
|
||||
###################################################################
|
||||
|
||||
record(ai, "$(P)$(R)test_ai")
|
||||
{
|
||||
field(DESC,"test record say: Hello World")
|
||||
}
|
||||
|
||||
Reference in New Issue
Block a user